          <caption id="ebcgh"><dt id="ebcgh"><map id="ebcgh"><rp id="ebcgh"><code id="ebcgh"><tbody id="ebcgh"></tbody></code></rp><abbr id="ebcgh"></abbr><td id="ebcgh"><colgroup id="ebcgh"><nav id="ebcgh"><fieldset id="ebcgh"><dd id="ebcgh"><option id="ebcgh"><dl id="ebcgh"><i id="ebcgh"></i></dl><datalist id="ebcgh"></datalist></option></dd></fieldset></nav></colgroup></td><p id="ebcgh"><datalist id="ebcgh"><small id="ebcgh"></small></datalist></p></map><tfoot id="ebcgh"></tfoot></dt></caption>
        1. 技术文章 | Article
          当前位置:首页 > 技术文章
          后备电池时间计算公式
          点击次数:245 发布时间:2018-04-13
            一般评标计算通用公式为转换为文字描述为下列公式已知单台UPS输出功率为30KVA等于24KW,UPS输出功率因数为0.81VA≈0.8W预计使用 12V-100AH 2组。
           
            每组电池数为32只,2组即为64只,电池单体数为6,UPS逆变效率为 0.94 计算方法,视在功率 30000 VA× 功率因数 0.8=24000W 24000W/ 64 只 * 6 * 0.94 =66.48 A 求出放电电流为 66.48 A 后 查表可知,当终止电压 1.75V 时 ,2H 放电电流为 67.9 A 和 66.48 zui接近 当 UPS 单机满负载 30KVA 时,64只100AH 满足约 2 小时电池后备工作时间以上电池的计算是基于和25℃的标准环境条件下的.
           
            后备电池配置计算方法一,UPS电源蓄电池容量的选配方法,算法在UPS电源运行中,如发生市电中断,蓄电池必须在用户所预期的时间内向逆变器提供足够的直流能源,以便在带额定输出负载的情况下,电池电压不致降到所允许的zui低临界放电电压以下.蓄电池实际可供使用容量与放电电流大小工作环境温度、存储时间长短等因素有密切的关系,只有在充分考虑上述因素之后,才能正确选择和确定蓄电池可供使用容量与标称容量的比率.